Read PLC signals and registers with Modbus TCP

Qynetic Edge reads coils, discrete inputs, holding registers and input registers over Modbus TCP. The device’s register map gives each raw value its meaning.

Match the register map to the device

Get the register map for the installed device and firmware. For each signal, identify the unit ID, read function, zero-based address, data type and scale. A 32-bit value occupies two registers, so check the byte and word order against a known reading.

Edge supports read functions 1 and 2 for coils and discrete inputs, and 3 and 4 for holding and input registers. The register functions can return signed or unsigned 16-bit and 32-bit integers, or a 32-bit floating-point value. The adapter connects over TCP and only issues reads.

Check how the manual numbers registers

A register label printed as 40001 can denote the first holding register. In that convention the starting address in a read request is zero. Some manuals already print the zero-based address. Confirm the convention for this model and compare a known value with the operator display.

Choose signals that survive polling

Edge timestamps the polling cycle locally. A contact that switches on and off between two reads can go unobserved. For production totals, look for a cumulative counter maintained by the PLC and find out when it resets. For a process measurement, check the reading interval against how quickly the process changes.